XS26-ISDd
Detalle del Producto Controladores de Seguridad Expandibles Serie XS26
Certificaciones
Amplificadores Compatibles
Donde sea aplicable, el rango máximo para modelos opuestos también depende de la longitud de la fibra.
Especificaciones
- IP Rating
- IP20
- Network View and Configure
- Yes
- Power
- DC
- Device Type
- Safety Controller
- In-Series Diagnostics
- Yes
- Safety Module Type
- Base Controller
- Expandable
- Yes
- LCD Display
- Yes
- Dimension (H x W x D in mm)
- 110 x 45 x 129
- Relative Humidity
- 90% @ 50° C
- Max Operating Temperature ( °C)
- 55
- Input Operation
- Simultaneous or Concurrent
- Number of Safe Inputs
- 26
- Input Configuration
- Configurable
- Number of Convertible Inputs
- 8
- Safety Input - Dual Channel (Dry Contact)
- 5-50 mA @ 24 V dc
- Safety Input - Dual Channel (Solid-State)
- 50 mA @ 15 - 30 V dc
- Safety Input - Reset
- 5-50 mA @ 24 V dc
- Independently Controlled Safe Outputs
- 4
- Output Configuration
- 2 OSSD Pairs
- Non Safe Output Configuration
- Up to 11 PNP
- Non Safe Output Rating
- 80 mA @ 24 V dc (individual) max for IOx; overcurrent protected, 500 mA @ 24 V dc for Sox
- Safe Output Rating
- OSSD 0.50 A max. @ 24 V dc
- Splittable Safe Output
- Yes
- Power Consumption
- 0.16 A (controller only); 3.6 A (bus load)
- Response Time (ms)
- See Software Configuration Summary
- Supply Voltage
- 24 V dc +/- 20%
- Terminal Type
- Screw
- Removable Terminals
- Yes
- Vibration
- 9-150 Hz at 1g occasional/0.5g continuous
- PL Rating
- e
- Safety Category Rating
- 4
- SIL Rating
- 3
- SISTEMA
- PFHd = 1.05 x 10-9
- THC Rating
- IIIC
- Safety Input - Single Channel
- 5-50 mA @ 24 V dc
- Input Resistance
- 150 Ω max. per lead
- E-Stops/Rope Pulls
- Yes
- Safety Mat
- Yes
- Motor Speed
- No
- Two-Hand Controls
- Yes
- Muting
- Yes
- Gate Switch (NC/NC) Input
- Yes
- Gate Switch (NC/NO) Input
- Yes
- Gate Switch (OSSD) Input
- Yes
- Light Curtains/Scanner with EDM Input
- Yes
- Light Curtains/Scanner without EDM Input
- Yes
- EtherNet/IP
- Yes
- Modbus/TCP
- Yes
- PCCC
- Yes
- PROFINET
- Yes
- EPLAN Status
- Published
- Recovery Time
- 250 (typical), 400 (max)
- EPLAN Original Sent Date
- 06/20/2022
Descargas
Archivos CAD
Documentación técnica
Date
Type
Size
Certificaciones
Date
Type
Size
Archivos con Datos del Producto
PLC Support Files
Date
Type
Size
Software
Date
Type
Size
EPLAN
Date
Type
Size
XS26-ISDd